European Standard EN13779: The Link between Outdoor Air Quality and Indoor Air Quality

EN13779 is the nearest thing to an IAQ standard, with built-in recommendations for outdoor air and indoor air which can include particulate and molecular filtration. As a relatively new standard for ventilation and room conditioning systems in non-residential buildings, EN 13779 is now a legally accepted standard in all EC member states. The standard sets out to achieve a comfortable and healthy indoor air quality in all seasons of the year at acceptable installation and operating costs, taking into consideration the outdoor air. This represents a major step forward, recognizing the importance of external air in achieving better indoor air quality and/or a healther environment .

Categories of Outdoor Air According to EN13779

Category Description Location
ODA 1 Pure air which may be only  temporarily dusty e.g. pollen Rural areas or sparsely populated villages
ODA 2 Outdoor air with high concentrations of gaseous pollutants and particulate matter Larger town with industry and polluted city center
ODA 3 Outdoor air with very high concentrations of gaseous pollutants and particulate matter Larget town with industry and polluted city center

Categories of Indoor Air According to EN13779

Catergory Description CO2 level ppm Outside Air m3/h/person
IDA 1 High indoor air quality < 400 > 54
IDA 2 Medium indoor air quality 400-600 36-54
IDA 3 Moderate indoor air quality 600-1000 22-36
IDA 4 Low indoor air quality > 1000 <22

EN13779 Meets EN779:2002 To recommend Filter Classes For Different Levels of ODA and IDA Categories

Outdoor Air Quality IDA 1 (High) IDA 2 (Medium) IDA 3 (Moderate) IDA 4 (Low)
ODA 1 (pure) F9 F8 F7 F5
ODA 2 (dust) F7 + F9 F6 + F8 F5 + F7 F5 + F6
ODA 3 (high concentrations
of dust and/or gases)
F7 + *GF + F9 F7 + *GF + F9 F5 + F7 F5 + F6

* GF= Gas Phase Filters


Recommended Products:
DriPak 2000 S
DriPak GF
VariCel EcoPak
VariCel VXL
VariSorb SAAFCity